Uptime calculator
The calculations run in the browser and require JavaScript. Fixed examples are shown.
Combined availability of several components
Everything runs in your browser; nothing is sent or stored.
- Enter a percentage in the "Availability percentage" field, or click one of the values in the "Common values" section, from 99% to 99.999%.
- The table shows the allowed downtime per day, week, month, and year, with the exact number of seconds next to each period.
- Copy all the results by clicking "Copy the results".
- In the "Availability percentage by downtime" section, enter the downtime and choose the time unit and the measurement period.
- In the "Combined availability of several components" section, enter the availability percentage of each component and choose whether the components are connected in series or in parallel.
- The definition of downtime, the measurement window, and the exclusions (such as planned maintenance) differ between providers. When you compare SLAs, compare these definitions too, not only the availability percentage.
- Our availability commitment is detailed in the service level agreement.
What an availability percentage means
The availability percentage is the share of the measurement period during which the service was up. Each additional 9 in the availability percentage cuts the allowed downtime by a factor of 10, so the difference between 99.9% and 99.99% is bigger than it looks at first glance. The allowed downtime also depends on the length of the measurement period, so at the same availability percentage, a 31-day month allows more downtime than a 28-day month.
Combined availability in series and in parallel
When a service depends on several components, such as a web server and its database, the combined availability in series is the product of the components' availability. For example, the combined availability of two components at 99.9% each is 99.8001%, which is about 17.5 hours of downtime a year. With components in parallel, such as two identical servers, the service goes down only when all the components are down at the same time, so the combined availability of two components at 99% each is 99.99%.
What to check in a service level agreement (SLA)
The availability percentage in a service level agreement is meaningful only together with the definitions in the agreement. Check what counts as downtime (for example, only a full outage or also a significant slowdown), what the measurement period is, and which cases are excluded from the calculation, such as planned maintenance or a fault on the customer's side. Also check how availability is measured and what compensation you get when the provider does not meet its commitment, for example a credit on your account.
Allowed downtime in a 365-day year
99% - 3 days, 15 hours, and 36 minutes.
99.5% - 1 day, 19 hours, and 48 minutes.
99.9% - 8 hours, 45 minutes, and 36 seconds.
99.95% - 4 hours, 22 minutes, and 48 seconds.
99.99% - 52 minutes and 34 seconds.
99.999% - 5 minutes and 15 seconds.
With our website and server monitoring service, you get an alert by email, SMS, or push notification when a check fails.
Uptime calculator FAQ
How much downtime does 99.9% availability allow per month and per day?
At 99.9% availability, an average month allows 43 minutes and 50 seconds of downtime, and a 30-day month allows 43 minutes and 12 seconds. A day allows about 1 minute and 26 seconds of downtime.
Is 99.9% yearly availability the same as 99.9% monthly availability?
No. Yearly availability of 99.9% is not the same as monthly availability at the same percentage. Under a yearly commitment, 8 hours of downtime in a single month does not breach the commitment, while under a monthly commitment, the allowed downtime in each month is limited to about 43 minutes.
Why is the availability percentage not shown as 100% even when the downtime is very short?
The availability percentage is shown with up to 5 digits after the decimal point, and any further digits are cut off without rounding. So even with 1 second of downtime a year, the availability percentage is shown as 99.99999%, and only a period with no downtime at all is shown as 100%.
Does the parallel calculation apply to two servers in the same data center?
For two servers in the same data center, the result of the parallel calculation may be higher than the actual availability. The calculation assumes that a fault in one component does not affect the other, but two servers that share the same power source, the same network, or the same software can go down together.
How do I calculate availability for a quarter or another period?
In the "Availability percentage by downtime" section, you can choose a quarter of 91.32 days in the "Measurement period" field, or choose "Other number of days" and enter the number of days in the period, for example 90. The number of days can be up to 3,660.